fire automatic alarm system, a large number of components are involved, and the response time of each component is a headache for us. The editor will summarize the time involved in this chapter to facilitate everyone to remember.
1. Control and display device
Device type | Action | Time | ||||||||||||||||||||||
Fire alarm controller | Fault alarm | 100s | ||||||||||||||||||||||
Fire alarm priority/secondary alarm | 10s | 4|||||||||||||||||||||||
Area display | Receive and display the alarm signal of the detector | 3s | ||||||||||||||||||||||
Fire linkage controller | Issuing control signal | 3s | ||||||||||||||||||||||
Fault Alarm | 100s | |||||||||||||||||||||||
Graphic Display Device | Receive the signal of the fire alarm controller and fire linkage controller | 3s | ||||||||||||||||||||||
Input/Output Module | Action indicator light on/off | 3s | ||||||||||||||||||||||
Gas fire extinguishing controller | Receive and display the feedback signal of the startup device | 10s | ||||||||||||||||||||||
Fault Alarm | 100s | |||||||||||||||||||||||
Fireproof Roller Shutter Controller | emits rolling shutter action sound and light alarm | 3s |
2. Detector
Device type | Action | time | |
line beam sensing fire detector | 0.9dB | does not issue an alarm signal | / |
1~10dB | Fire alarm | 10s | |
11.5dB | Fire alarm or fault | 100s | |
Pipeline Sampling style aspiration fire detector | fire alarm confirmation light lit | 120s | |
point flame detector, image fire detector | fire alarm confirmation light lit | 30s 3 | |
Combustible gas detection alarm system | Combustible gas detector | Fire alarm confirmation lamp lit | 30s |
Fault indicator light lit | 10 0s | ||
Electric fire monitoring system | Remaining current type electrical fire monitoring detector | Fire alarm confirmation light lit | 30s |
Temperature measurement type electrical fire monitoring detector | Fire alarm confirmation light lit | 40s | |
Fault arc detector | 1s produces 9 and less than half cycle fault arcs | not alarm | / |
1s generates 14 or more half cycle faults Arc | Fire alarm confirmation light lit | 30s |
3. Fire alarm, fire emergency broadcast
Device type | Continuous working time |
Fire sound and light alarm | 8s~20s |
Fire emergency broadcast | 10s~30s |
expansion: " Disaster Alarm Controller " fire alarm controller needs to receive two or more fire alarm signals from the same detector (area) to determine that the fire alarm signal is issued, the following requirements should also be met: (1) When the controller receives the first fire alarm signal, it should send out a fire alarm signal or a fault alarm signal and indicate the corresponding part, but it cannot enter the fire alarm state.(2) After receiving the first fire alarm signal, when the controller receives the required subsequent fire alarm signal within 60s, it should emit a fire alarm sound and light signal and enter the fire alarm state. (3) After receiving the first fire alarm signal and the controller still fails to receive the required subsequent fire alarm signal within 30 minutes, the first fire alarm signal should be automatically reset.