When debugging the automatic fire alarm system, a large number of components are involved, and the response time of each component is a headache for us. The editor will summarize the time involved in this chapter to facilitate everyone to remember. 1.

2025/05/1105:19:36 hotcomm 1499
When debugging the

fire automatic alarm system, a large number of components are involved, and the response time of each component is a headache for us. The editor will summarize the time involved in this chapter to facilitate everyone to remember.

When debugging the automatic fire alarm system, a large number of components are involved, and the response time of each component is a headache for us. The editor will summarize the time involved in this chapter to facilitate everyone to remember. 1. - DayDayNews

1. Control and display device

4html l15

Device type

Action

Time

Fire alarm controller

Fault alarm

100s

Fire alarm priority/secondary alarm

10s

Area display

Receive and display the alarm signal of the detector

3s

Fire linkage controller

Issuing control signal

3s

Fault Alarm

100s

Graphic Display Device

Receive the signal of the fire alarm controller and fire linkage controller

3s

Input/Output Module

Action indicator light on/off

3s

Gas fire extinguishing controller

Receive and display the feedback signal of the startup device

10s

Fault Alarm

100s

Fireproof Roller Shutter Controller

emits rolling shutter action sound and light alarm

3s

2. Detector

Device type

Action

time

line beam sensing fire detector

0.9dB

does not issue an alarm signal

/

1~10dB

Fire alarm

10s

11.5dB

Fire alarm or fault

100s

Pipeline Sampling style aspiration fire detector

fire alarm confirmation light lit

120s

point flame detector, image fire detector

fire alarm confirmation light lit

30s

3

Combustible gas detection alarm system

Combustible gas detector

Fire alarm confirmation lamp lit

30s

Fault indicator light lit

10 0s

Electric fire monitoring system

Remaining current type electrical fire monitoring detector

Fire alarm confirmation light lit

30s

Temperature measurement type electrical fire monitoring detector

Fire alarm confirmation light lit

40s

Fault arc detector

1s produces 9 and less than half cycle fault arcs

not alarm

/

1s generates 14 or more half cycle faults Arc

Fire alarm confirmation light lit

30s

3. Fire alarm, fire emergency broadcast

Device type

Continuous working time

Fire sound and light alarm

8s~20s

Fire emergency broadcast

10s~30s

expansion: " Disaster Alarm Controller " fire alarm controller needs to receive two or more fire alarm signals from the same detector (area) to determine that the fire alarm signal is issued, the following requirements should also be met: (1) When the controller receives the first fire alarm signal, it should send out a fire alarm signal or a fault alarm signal and indicate the corresponding part, but it cannot enter the fire alarm state.(2) After receiving the first fire alarm signal, when the controller receives the required subsequent fire alarm signal within 60s, it should emit a fire alarm sound and light signal and enter the fire alarm state. (3) After receiving the first fire alarm signal and the controller still fails to receive the required subsequent fire alarm signal within 30 minutes, the first fire alarm signal should be automatically reset.