Multi-line maintenance E1 fault

E1 high voltage protection

fault display: outdoor unit main board , indoor unit wire controller, indoor unit receiving light board display applicable model: GMV series

fault judgment conditions and methods:

through high-voltage sensor detection system Real-time high voltage or detect whether the high voltage switch operates to judge. If the sensor detects that the high voltage value is greater than 65°C or the high voltage switch is disconnected, it is judged that the high voltage is too high and the system shuts down for protection.

E1 fault in multi-line maintenance E1 high-voltage protection fault display: the outdoor unit main board, indoor unit wire controller, and indoor unit receiving light board display applicable models. Possible reasons: 1. The outdoor unit stop valve is not opened; 2. The operating - DayDayNews

Possible reasons :

1. The outdoor unit stop valve is not open;

2. The operating environment temperature is too high and the ventilation at the installation location is poor;

3. The system refrigerant is too much;

4. The outdoor or indoor fan is abnormal (cooling/heating mode) ;

5. The indoor unit filter or air duct is blocked (heating mode);

6. The high-pressure switch operates abnormally;

7. The high-pressure sensor is abnormal;

8. The system pipeline is blocked.

E1 fault in multi-line maintenance E1 high-voltage protection fault display: the outdoor unit main board, indoor unit wire controller, and indoor unit receiving light board display applicable models. Possible reasons: 1. The outdoor unit stop valve is not opened; 2. The operating - DayDayNews

E1 fault in multi-line maintenance E1 high-voltage protection fault display: the outdoor unit main board, indoor unit wire controller, and indoor unit receiving light board display applicable models. Possible reasons: 1. The outdoor unit stop valve is not opened; 2. The operating - DayDayNews

Multi-line maintenance E2 fault

E2: Exhaust low temperature protection

Fault display: Outdoor unit main board, indoor unit wire controller, indoor unit receiving light board display

Applicable model: GMV series

Fault judgment conditions and methods:

Pass detection Compressor exhaust temperature and high pressure value, if the difference between the exhaust temperature and high pressure value is lower than 10℃, it will shut down for protection.

Possible reasons:

1. Too much refrigerant in the system;

2. The compressor exhaust temperature sensing package detects abnormally;

3. In the cooling mode, the electronic expansion action of the indoor unit is abnormal;

4. In the heating mode, the outdoor electronic expansion valve behaves abnormally.