Brand: WANLIN-GA900 User Information Transmission Device Model: WANLIN-GA900 User Information Transmission Device Product Description: WANLIN-GA900 User Information Transmission Device Instruction Manual Figure Number: WANLIN-GA900 Version Number: V1.0 Produced: Review: Approval:

Brand: WANLIN-GA900 User Information Transmission Device Model: WANLIN-GA900 User Information Transmission Installation Product Description: WANLIN-GA900 User Information Transmission Device

Instruction Manual


Figure number: WANLIN-GA900
Version number: V1.0


Preparation:

Review:

batch Accepted:

Wanlin (Beijing) Fire Protection Technology Co., Ltd.



Directory . WANLIN-GA900 User Information Transmission Device Product Introduction 1. WANLIN-GA900 User Information Transmission Device System Diagram 1. User Information Transmission Device Installation Method 1. User Information Transmission Device Installation Method 1. User Information Transmission Device Installation Method 1 1. Main functions 1. Product base performance parameters 2. indicator light function 2. LCD display 3. key function introduction 3 . 1 box terminal 50. external dimensions and installation diagram 51. after-sales service instructions 6


1.
WANLIN-GA900 User Information Transmission Device Product Introduction

User Information Transmission Device is the core front-end device of the urban fire remote monitoring system, which is used to obtain and transmit various user alarm information and equipment status information obtained from the user fire control host . It is the core equipment of the urban fire remote monitoring system. The urban fire remote monitoring system is a system that connects, processes and manages fire alarm information, building firefighting facilities operation status information, and fire safety management information of Internet of Things users, sends confirmed fire alarm information to the urban fire communication command center or other police reception centers, provides inquiries for public security fire departments, and provides information services for networked users. The remote monitoring system is composed of a user information transmission device, an alarm transmission network, an alarm acceptance system, an information query system, a user information service system, and related terminals and interfaces.
2.
User Information Transmission Device System Diagram


Note: WANLIN-GA900 The user information transmission device is the core equipment of the urban fire remote monitoring center. It transmits data with the building fire alarm host through RS485 or CAN bus. All alarm information of the building fire alarm host is uploaded to the user information transmission device, and the user information device is then uploaded to the remote monitoring center through the network interface. The user information transmission device and the remote monitoring center transmit data through TCP/IP or wireless means.
3.
WANLIN-GA900 User Information Transmission Device Installation Method
User Information Transmission Device adopts a wall-mounted installation, metal shell, and display design. It has the advantages of easy installation, strong anti-interference ability, and easy use. The product has extensible functions, and the product also has the function of remote upgrade, which is convenient for applications in various environmental places.
4.
Main functions
Ø Extended function: The device has an extensible interface function to meet the use of special environments
Ø Remote upgrade: The device has the function of remote software upgrade.
Ø Display function: display status information, fault information, and alarm information of the monitored point.
Ø Storage function: Store fault information and alarm information of the monitored point and the machine.
Ø Status display: When the device has data transmission, it can display various data information status.
Ø Address setting: This machine has a unique encoding number.
Ø Main and backup power function: When the main power fails, automatically switch to the backup power working state, and the main power will resume normal switching to the main power working.
Ø Power reserve work: can standby for more than 8 hours under normal working conditions with full charge.
Ø Self-test function: used to detect whether the device's lamp, LCD, audio devices and communication link are normal.
Ø Reset function: Can alarm information and fault information of the machine
Ø Voice silence function: When the device is in a fire or fault state, the device starts up, press Voice to mute.

Brand: WANLIN-GA900 User Information Transmission Device Model: WANLIN-GA900 User Information Transmission Installation Product Description: WANLIN-GA900 User Information Transmission Device

Instruction Manual


Figure number: WANLIN-GA900
Version number: V1.0


Preparation:

Review:

batch Accepted:

Wanlin (Beijing) Fire Protection Technology Co., Ltd.



Directory . WANLIN-GA900 User Information Transmission Device Product Introduction 1. WANLIN-GA900 User Information Transmission Device System Diagram 1. User Information Transmission Device Installation Method 1. User Information Transmission Device Installation Method 1. User Information Transmission Device Installation Method 1 1. Main functions 1. Product base performance parameters 2. indicator light function 2. LCD display 3. key function introduction 3 . 1 box terminal 50. external dimensions and installation diagram 51. after-sales service instructions 6


1.
WANLIN-GA900 User Information Transmission Device Product Introduction

User Information Transmission Device is the core front-end device of the urban fire remote monitoring system, which is used to obtain and transmit various user alarm information and equipment status information obtained from the user fire control host . It is the core equipment of the urban fire remote monitoring system. The urban fire remote monitoring system is a system that connects, processes and manages fire alarm information, building firefighting facilities operation status information, and fire safety management information of Internet of Things users, sends confirmed fire alarm information to the urban fire communication command center or other police reception centers, provides inquiries for public security fire departments, and provides information services for networked users. The remote monitoring system is composed of a user information transmission device, an alarm transmission network, an alarm acceptance system, an information query system, a user information service system, and related terminals and interfaces.
2.
User Information Transmission Device System Diagram


Note: WANLIN-GA900 The user information transmission device is the core equipment of the urban fire remote monitoring center. It transmits data with the building fire alarm host through RS485 or CAN bus. All alarm information of the building fire alarm host is uploaded to the user information transmission device, and the user information device is then uploaded to the remote monitoring center through the network interface. The user information transmission device and the remote monitoring center transmit data through TCP/IP or wireless means.
3.
WANLIN-GA900 User Information Transmission Device Installation Method
User Information Transmission Device adopts a wall-mounted installation, metal shell, and display design. It has the advantages of easy installation, strong anti-interference ability, and easy use. The product has extensible functions, and the product also has the function of remote upgrade, which is convenient for applications in various environmental places.
4.
Main functions
Ø Extended function: The device has an extensible interface function to meet the use of special environments
Ø Remote upgrade: The device has the function of remote software upgrade.
Ø Display function: display status information, fault information, and alarm information of the monitored point.
Ø Storage function: Store fault information and alarm information of the monitored point and the machine.
Ø Status display: When the device has data transmission, it can display various data information status.
Ø Address setting: This machine has a unique encoding number.
Ø Main and backup power function: When the main power fails, automatically switch to the backup power working state, and the main power will resume normal switching to the main power working.
Ø Power reserve work: can standby for more than 8 hours under normal working conditions with full charge.
Ø Self-test function: used to detect whether the device's lamp, LCD, audio devices and communication link are normal.
Ø Reset function: Can alarm information and fault information of the machine
Ø Voice silence function: When the device is in a fire or fault state, the device starts up, press Voice to mute.
Ø Permission settings: Perform corresponding functional operations according to permissions

5.
Product basic performance parameters

Input power

0W---40W

channel RS485, 1 channel RS232 and 1 channel switch

-to-one connection

V/7.0AH After power off, standby is greater than 8 hours

.5 inch monochrome LCD screen

℃-+40℃, humidity: 95%RH

Product

name

name

User information transmission device

Model

WANLIN-GA900

Input parameter

AC 220 V ± 20% 50Hz

Communication interface

Output parameters

Communication method

TCP communication

Communication line

Super five network cable

Super five network cable html l3

upload interface

RJ45 network interface

management node number

report Alarm

sound and light display

password

Display

Operation

1 key operation method

environment

Protection level

IP30

Execution standard

GB26875-2011 "User Information Transfer Device"

External Dimension

length × width × height: 400mm × 120mm × 280mm

Installation method

Wall-mounted

. indicator light function

When the system is working abnormally,

Huang

11111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111111 The content can be displayed with local information, real-time, and received faults, alarm information, system record information, etc. of the alarm host.
Ø can be operated and controlled to display different contents through keys;
Ø After the self-test is completed, the content before the self-test is displayed;
Ø The self-test process shows specific characters from line 1 to line 4 in sequence
8. key function introduction
device has a total of 6 valid keys, namely: silence, reset, self-test, confirmation, response and manual alarm keys.The operation password is: 1111, and the super password is: 2222. When the
system is running normally, the default functions of each key are displayed on the screen are as follows:
1. The silence button can mute the buzzer. The buzzer will sound again after a new alarm or failure. After pressing
, the user will be prompted to enter the silence password. The prompt is shown in Figure 2:


Figure 2 Enter password interface After entering this interface, the silence button can shift the password bit to control the operation, press the reset key to achieve one operation, and the self-test key to achieve one operation. Each bit can change the password between 0 and 9, confirm the key to confirm the input, and if the password is correct, the next operation can be performed (Figure 3). If the password is incorrect, you can re-enter (Figure 4).


Figure 3 Correct password prompt


Figure 4 Password error prompt
Press the answer key to return to the normal monitoring interface.
2. The reset button can remove alarm and fault status and restore the system to normal status. After pressing
, the user will be prompted to enter the reset password. The password input operation is the same as above.
3. The self-test button can automatically check all hardware functions such as indicator lights, buzzers, LCD screens, etc. After pressing
, the user will be prompted to enter the self-test password. The password input operation is the same as above.
3. The confirm button can respond to the inspection commands of the monitoring center. After pressing
, the user will be prompted to enter the confirm password. The password input operation is the same as above.
4. The answer button can respond to the monitoring center's post check command. After pressing
, the user will be prompted to enter the reply password. The password input operation is the same as above.
5. The manual alarm button can manually make the system work in a manual fire alarm state. After pressing
, the user will be prompted to enter the alarm password. The password input operation is the same as above.
6. Press and hold the silence button for more than 5 seconds to enter the system information query and system record query interface. Under this interface, sound silencing, resetting, and self-test represent options 1, 2, and 3 respectively. Press the corresponding keys to enter the lower interface.
9.
In-box terminal block
Ø CAN terminal block: CH, CL;
Ø RS485 terminal: A, B
Ø Serial terminal block DB9
Ø Ethernet interface RJ45
Ø Fire alarm input interface
Ø Relay output interface
Ø LORA wireless expansion interface
Ø GPRS wireless expansion interface
Ø 5V power output interface
10.
external dimensions and installation diagram

external dimensions diagram Installation diagram

11.
After-sales service instructions
Please contact the dealer in time after this product is damaged by natural lightning strikes and perform free repair or replacement during the shelf life. Paid maintenance is implemented outside the warranty.
The following situations do not fall within the scope of free maintenance:
1. Product damage caused by abnormal human operation.
2. Product damage caused by failure to install and use in accordance with national standards or instructions.
3. Product damage caused by irresistible reasons other than lightning strikes.
4. Product damage caused by destructive tests.
5. Products that lack invoices, barcodes, production dates, and products that exceed their shelf life.

The operation password is: 1111, and the super password is: 2222. When the
system is running normally, the default functions of each key are displayed on the screen are as follows:
1. The silence button can mute the buzzer. The buzzer will sound again after a new alarm or failure. After pressing
, the user will be prompted to enter the silence password. The prompt is shown in Figure 2:


Figure 2 Enter password interface After entering this interface, the silence button can shift the password bit to control the operation, press the reset key to achieve one operation, and the self-test key to achieve one operation. Each bit can change the password between 0 and 9, confirm the key to confirm the input, and if the password is correct, the next operation can be performed (Figure 3). If the password is incorrect, you can re-enter (Figure 4).


Figure 3 Correct password prompt


Figure 4 Password error prompt
Press the answer key to return to the normal monitoring interface.
2. The reset button can remove alarm and fault status and restore the system to normal status. After pressing
, the user will be prompted to enter the reset password. The password input operation is the same as above.
3. The self-test button can automatically check all hardware functions such as indicator lights, buzzers, LCD screens, etc. After pressing
, the user will be prompted to enter the self-test password. The password input operation is the same as above.
3. The confirm button can respond to the inspection commands of the monitoring center. After pressing
, the user will be prompted to enter the confirm password. The password input operation is the same as above.
4. The answer button can respond to the monitoring center's post check command. After pressing
, the user will be prompted to enter the reply password. The password input operation is the same as above.
5. The manual alarm button can manually make the system work in a manual fire alarm state. After pressing
, the user will be prompted to enter the alarm password. The password input operation is the same as above.
6. Press and hold the silence button for more than 5 seconds to enter the system information query and system record query interface. Under this interface, sound silencing, resetting, and self-test represent options 1, 2, and 3 respectively. Press the corresponding keys to enter the lower interface.
9.
In-box terminal block
Ø CAN terminal block: CH, CL;
Ø RS485 terminal: A, B
Ø Serial terminal block DB9
Ø Ethernet interface RJ45
Ø Fire alarm input interface
Ø Relay output interface
Ø LORA wireless expansion interface
Ø GPRS wireless expansion interface
Ø 5V power output interface
10.
external dimensions and installation diagram

external dimensions diagram Installation diagram

11.
After-sales service instructions
Please contact the dealer in time after this product is damaged by natural lightning strikes and perform free repair or replacement during the shelf life. Paid maintenance is implemented outside the warranty.
The following situations do not fall within the scope of free maintenance:
1. Product damage caused by abnormal human operation.
2. Product damage caused by failure to install and use in accordance with national standards or instructions.
3. Product damage caused by irresistible reasons other than lightning strikes.
4. Product damage caused by destructive tests.
5. Products that lack invoices, barcodes, production dates, and products that exceed their shelf life.

name

function Can

running light-green

After power on, the program flashes periodically when it is normal to run

check light-yellow

Fire alarm light-red

Received that the check name is on

Fire alarm light-red

html ml0 After receiving the fire alarm information from the alarm host, light up

Manual fire alarm

Manual alarm key is valid and lit up

Connection light-green

Connection light-green

Connection light with the alarm host is normal, flashing when there is data transmission

Link light Green

wired connection with the monitoring center is normal, flashing

link two light Green

wireless connection with the monitoring center is normal, flashing

link fault light Yellow

link fault light Yellow

disconnected from the monitoring center is normal, flashing

system fault light Yellow

main power fault light Yellow

main power fault light When the main power is working abnormally,

power fault light Yellow

connection fault light Yellow

fault light Yellow