1·The alcohol safety meter should be installed in a place that is easily visible and easy to operate, such as the kitchen office or doorway, and installed on the wall between the stove and the location where mobile signal reception is normal.
2·Cannot be installed in a humid environment, or in a place with strong current, strong magnetism and other signal interference.
3. The power cord of Chun'an Instrument should use RVV copper core wire of more than 0.75 square meters. The power socket supplies power separately and cannot be used in the same line as high-power electrical appliances to prevent damage caused by voltage instability.
4. The signal lines used by the liquid level meter , gas detector and other sensors supporting the alcohol safety instrument should use more than 0.5 square meters of to shield the signal line , and the signal line cannot be routed in the same pipeline as the power line to prevent Signal interference.
5·After the installation is completed, the excess wiring ports must be tightened and the outer cover must be closed to prevent damage caused by moisture.
6. Before installation, the liquid level meter should be powered on and calibrated to zero, and the probe rod should be straightened as much as possible before inserting it into the storage tank. After inserting into the storage tank, the bottom of the probe rod and the bottom of the tank must not be in closed contact, otherwise the liquid level cannot be detected.
7· combustible gas detector should be installed within 0.3 meters from the ground when detecting liquid fuel volatile gases such as liquefied gas and alcohol-based fuel. When detecting natural gas and artificial gas , it should be installed 0.3 meters from the roof. Within the location, when detecting leakage from burning appliances, it should be installed within 0.5 to 1.5 meters from the burning appliance.
8·When installing the outlet valve, it is best to install it in the order of ball valve>>temperature control valve>> solenoid valve (DC24V normally open)>>oil pipe.
9·Standardized wiring.
2. Precautions for using the alcohol safety meter:
1. Make sure that the alcohol safety meter is not powered on 24 hours a day . It is recommended to cut off the power and restart it once a week to ensure a normal network connection.
2. Before refueling, the filling valve should be opened remotely and closed remotely after the filling is completed.
3·Regular maintenance, recommends maintenance once a month, check whether various functions and accessories can work normally.
4·For function usage and other operating instructions, please refer to the device manual.